FLOODED DEEP CYCLE BATTERY |
S6 L16-HC |
|
|
| Series | FLA SERIES 4000 | Warranty | 3 Years |
|---|---|---|---|
| Volts | 6 | Design | L16 |
| Cells | 3 | Plates/Cell | 17 |
| Terminal Type | LT | ||
| Included Hardware | S/S Hex Cap Screw, Nut, Lock & Flat Washer | ||
| Size & Thread | 5/16"-18 | ||
| Cables | Optional: 19" 4/0 interconnect cable | ||
| Charge | Discharge | |
|---|---|
| Charge Voltage Range | 2.45-2.5 V/cell @ 25°C (77°F) |
| Float Voltage Range | 2.25 V/cell @ 25°C (77°F) |
| Recommended Charge Current | 50 A |
| Maximum Charge Current | 85 A |
| Self-Discharge Rate | 5%-10% per month at 25°C (77°F) |
| Capacity | |
|---|---|
| Cold Crank Amps (CCA) 0°F / -18°C | 1040 |
| Marine Crank Amps (MCA) 32°F / 0°C | 1299 |
| Reserve Capacity (RC @ 25A) | 861 Minutes |
| Reserve Capacity (RC @ 75A) | 226 Minutes |
| Capacity Affect by Temperature | 40°C (104°F) |
25°C (77°F) |
0°C (32°F) |
-15°C (5°F) |
|---|---|---|---|---|
| 105% | 100% | 75% | 50% |
| Hour Rate | Capacity / AMP Hour | Current / AMPs |
|---|---|---|
| @ 100 Hour Rate | 512 AH | 5.12 A |
| @ 72 Hour Rate | 498 AH | 6.92 A |
| @ 50 Hour Rate | 481 AH | 9.61 A |
| @ 20 Hour Rate | 445 AH | 22.25 A |
| @ 15 Hour Rate | 418 AH | 27.89 A |
| @ 10 Hour Rate | 401 AH | 40.05 A |
| @ 8 Hour Rate | 383 AH | 47.84 A |
| @ 5 Hour Rate | 356 AH | 71.20 A |
| @ 1 Hour Rate | 209 AH | 209.15 A |
| Specifications | |||
|---|---|---|---|
| Weight | 55.5 kg | 122.5 lbs | |
| Length | 318 mm | 12.5" | |
| Width | 181 mm | 7.13" | |
| Height Incl. Term. | 425.5 mm | 16.75" | |
| Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components. | |||
| Electrolyte Reserve | 57 mm | 2.25" | |
|---|---|---|---|
| Container | High Density Polypropylene | ||
| Cover | High Density Polypropylene | ||
| Handles | Rope / Plastic Handle | ||
|
|||
Cycle Life vs. Depth of Discharge
Voltage vs. Depth of Discharge
Detailed Illustration