FLOODED DEEP CYCLE BATTERY |
S12 185 |
|
|
| Series | FLA SERIES 4000 | Warranty | 3 Years |
|---|---|---|---|
| Volts | 12 | Design | 921 |
| Cells | 6 | Plates/Cell | 11 |
| Terminal Type | DT | ||
| Included Hardware | Stainless Steel K-Lock Nut | ||
| Size & Thread | 5/16"-18 | ||
| Cables | Optional: 19" 4/0 interconnect cable | ||
| Charge | Discharge | |
|---|---|
| Charge Voltage Range | 2.45-2.5 V/cell @ 25°C (77°F) |
| Float Voltage Range | 2.25 V/cell @ 25°C (77°F) |
| Recommended Charge Current | 25 A |
| Maximum Charge Current | 40 A |
| Self-Discharge Rate | 5%-10% per month at 25°C (77°F) |
| Capacity | |
|---|---|
| Cold Crank Amps (CCA) 0°F / -18°C | 810 |
| Marine Crank Amps (MCA) 32°F / 0°C | 1013 |
| Reserve Capacity (RC @ 25A) | 406 Minutes |
| Reserve Capacity (RC @ 75A) | 107 Minutes |
| Capacity Affect by Temperature | 40°C (104°F) |
25°C (77°F) |
0°C (32°F) |
-15°C (5°F) |
|---|---|---|---|---|
| 105% | 100% | 75% | 50% |
| Hour Rate | Capacity / AMP Hour | Current / AMPs |
|---|---|---|
| @ 100 Hour Rate | 279 AH | 2.79 A |
| @ 72 Hour Rate | 265 AH | 3.68 A |
| @ 50 Hour Rate | 250 AH | 5 A |
| @ 20 Hour Rate | 210 AH | 10.5 A |
| @ 15 Hour Rate | 200 AH | 13.3 A |
| @ 10 Hour Rate | 185 AH | 18.48 A |
| @ 8 Hour Rate | 181 AH | 22.58 A |
| @ 5 Hour Rate | 166 AH | 33.18 A |
| @ 1 Hour Rate | 84 AH | 84 A |
| Specifications | |||
|---|---|---|---|
| Weight | 52 kg | 114.5 lbs | |
| Length | 391 mm | 15.38" | |
| Width | 178 mm | 7" | |
| Height Incl. Term. | 365 mm | 14.38" | |
| Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components. | |||
| Electrolyte Reserve | 51 mm | 2" | |
|---|---|---|---|
| Container | Polypropylene | ||
| Cover | Polypropylene | ||
| Handles | Rope / Plastic Handle | ||
|
|||
Voltage vs. Depth of Discharge
Detailed Illustration