Skip to main content

FLOODED DEEP CYCLE BATTERY

6 FS 145

Series FS Warranty 1 Year
Volts 6 Design GC2H
Cells 3 Plates/Cell 17
Terminal Type DT
Included Hardware Stainless Steel K-Lock Nut
Size & Thread 5/16"-18
Charge
Charge Voltage Range 2.45-2.5 V/cell @ 25°C (77°F)
Float Voltage Range 2.25 V/cell @ 25°C (77°F)
Self-Discharge Rate 5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -18°C 710
Marine Crank Amps (MCA) 32°F / 0°C 888
Reserve Capacity (RC @ 25A) 524 Minutes
Reserve Capacity (RC @ 75A) 144 Minutes
Capacity Affect by Temperature 40°C
(104°F)
25°C
(77°F)
0°C
(32°F)
-15°C
(5°F)
105% 100% 75% 50%
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 320 AH 3.2 A
@ 72 Hour Rate 315 AH 4.38 A
@ 50 Hour Rate 298 AH 5.95 A
@ 20 Hour Rate 250 AH 12.5 A
@ 15 Hour Rate 238 AH 15.83 A
@ 10 Hour Rate 220 AH 22 A
@ 8 Hour Rate 215 AH 26.88 A
@ 5 Hour Rate 198 AH 39.5 A
@ 1 Hour Rate 100 AH 100 A

Ampere hour capacity ratings based on specific gravity of 1.280 at 27°C (80°F).
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.

Specifications
Weight 32 kg 70.5 lbs
Length 259 mm 10.19"
Width 181 mm 7.13"
Height Incl. Term. 290 mm 11.4"
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components.
Electrolyte Reserve 28.6 mm 1.125"
Container Polypropylene
Cover Polypropylene
Handles Top Molded Strap Brackets
  • Plastics are UL94 HB (UL94-V2 available)
  • Plastics are impact copolymer rated to ASTM D256, D5420
  • Vented design with integral flame arrestor vent caps

Cycle Life vs. Depth of Discharge

Voltage vs. Depth of Discharge

Detailed Illustration

Rev.#2 | August 2024